Installation and Wiring

3-3

1503-UM051D-EN-P – June 2013

OEM

The IntelliVAC may be ordered as an OEM component. This allows

the OEM to mount the components in a configuration most suitable

to the motor controller equipment layout. Care must be exercised to

ensure the IntelliVAC has adequate ventilation provided around it.

Refer to Figure 3.2 for mounting the IntelliVAC. It is recommended

that a minimum of 1.5 inches (38.1mm) of free air space be provided

between the IntelliVAC and any solid barrier above or below.

The OEM is responsible for controller fusing, motor overload

protection, control devices (eg.

Start/Stop push buttons), and wiring

between the IntelliVAC and 1502 vacuum contactor (using optional

wire harness). Wiring and mounting for optional items, such as

TDUV Capacitor are also the OEM’s responsibility. Refer to Figure

3.3 or 3.4 for basic connections.

An optional EMI filter is required to meet CE EMC requirements

(refer to Chapter 6 for recommended type).

38.1

(1.50)

38.1

(1.50)

6.4 (0.25)

Additional Modules

(as required)

Minimum bottom clearance

Minimum top clearance

Dimensions in mm (inches)

38.1

(1.50)

38.1

(1.50)

6.4 (0.25)

Additional Modules

(as required)

Minimum bottom clearance

Minimum top clearance

Dimensions in mm (inches)

Figure 3.2 – Typical Mounting Configurations


Note:

Adjacent IntelliVAC modules may be mounted with a

minimum separation of 6.4 mm (0.25 inches).