Typical contactor drop-out times, Appendix – Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual
Page 41

Appendix
A
1503-UM051D-EN-P – June 2013
Typical Contactor Drop-out Times
The contactor drop-out times shown in the following table are typical
values used when the power fuses are provided as part of a complete
MV controller from Rockwell Automation. The recommendations
are based on Ferraz Shawmut power fuses. Other fuse types may
require alternate drop-out time settings.
Table A.1 – Contactor Drop-out Times
Fuse Rating
Contactor Drop-out Time (msec)
Voltage
Current
400A
800A
2R
3R
4R
6R
9R
12R
18R
19R
50
24R
100
32R
240
38R
50
48X
75
57X
200
2 x 24R
100
2 x 32R
240
< 5000
2 x 38R
240 *
20E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E
250E
300E
50
350E
75
400E
100
450E
130
500E
50
600E
75
750E
200
< 5000
900E
240 *
Fuse not suitable for use with 400A contactor.