Monitoring and Troubleshooting

5-3

1503-UM051D-EN-P – June 2013

Table 5.B – IntelliVAC Status Indication (Series B design)

Module Status

Contactor Status

Conditions

XY

Description

LED Color

Relay

LED Color

Relay

Normal

Healthy Module and Contactor OPEN

Green

Closed

Off

Open

Normal

Healthy Module and Contactor CLOSED

Green

Closed

Yellow

Closed

Warning

Invalid Command Present ^

Yellow

Closed

Off

Open

Warning

Mechanical Latch Fail to Trip

Yellow

Open

Yellow

Closed

Fault

Power Up with Contactor CLOSED

Red – Flash 2 [

Open

Yellow

Closed

Fault

Contactor Fails to Pick Up

Green

Open

Red – Flash 1 Z

Open

Fault

Contactor Drop Out During Hold

Green

Open

Red – Flash 2 [

Open

Fault

Long Contactor Drop Out Time

Green

Open

Red – Flash 3 Z

Open

Fault

Microcontroller Malfunction

Red

Open

Red

Open

Fault

Power Up with Invalid Dip Switch Configuration

Red – Flash 1 ›

Open

Off

Open

Fault

Undervoltage with a CLOSE Command Present

Red

Open

Off

Open

X

Warning = Recoverable Condition – Remove and retry offending signal

Y

Fault = Non-recoverable condition – Module power must be removed and re-applied.

Z

Flash 1 = 1 Flash Red LED followed by a pause.

[

Flash 2 = 2 Consecutive Red LED flashes followed by a pause.

\

Flash 3 = 3 Consecutive Red LED flashes followed by a pause.

]

EH = Only for Electrically Held Contactor

^

Invalid Command Types:

1. Close, Jog or Trip commands present during power up sequence.

2. Close or Jog command re-applied too quickly (before contactor opening sequence is verified).

Allow at least 60 msec, plus drop out delay time, before re-applying these signals.

NOTE:

Contactor will only respond to a close command re-applications after the re-start delay timer has expired.

3. Close and Trip commands present simultaneously (valid with Mechanical Latch contactors only).