Wiring guidelines mechanically latched contactors – Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual

Page 26

Advertising
background image

3-14

Installation and Wiring

1503-UM051D-EN-P – June 2013


IntelliVAC control may be used for mechanically latched contactors.

A momentary control signal is needed to close the contactor, and a

second momentary control signal is needed to open the contactor.

The momentary open/close commands must be at least 50

milliseconds in duration.

Refer to Figure 3.12 for a typical mechanical latch control scheme.

Note:

1. A mechanically latched contactor may already be closed when

power is applied to the IntelliVAC control module.

2. It is permissible to apply an open command to the IntelliVAC

module as power is re-applied.

Refer to Table 3.A for recommended fuse sizing.