Chapter 4 – setup and commissioning, Intellivac configuration, Setup and commissioning – Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual

Page 31: Chapter

Advertising
background image

Chapter

4

1503-UM051D-EN-P – June 2013

Setup and Commissioning


IntelliVAC Configuration

The IntelliVAC module is configured for a specific application by

setting DIP switches. They are accessed by loosening the two

screws on the front of the unit, and removing the cover by sliding it

forward. The switches are found on the front edge of the IntelliVAC

circuit board (see Figure 4-1). There are 12 switches, with number 1

being at the top next to the mini DIN connector. (Refer to Table 4.B).

I M P O R T A N T

I M P O R T A N T

Remove power from the module before

removing the cover and before changing the

DIP switch settings. The new settings are

recognized only on power-up.

Status Relay Outputs

Interface Connections

Ground Stud (Series A)

EEPROM Programming Port

(Mini DIN Connector)

DIP Switches

Ground Stud (Series B)

Supply Power Input

Internal Control Fuse

Status Relay Outputs

Interface Connections

Ground Stud (Series A)

EEPROM Programming Port

(Mini DIN Connector)

DIP Switches

Ground Stud (Series B)

Supply Power Input

Internal Control Fuse

Figure 4.1 – DIP Switch and Connector Locations

An IntelliVAC unit shipped separately from the factory will have a

default configuration per Table 4.A.

Table 4.A – DIP Factory Default Settings

DIP switch

Description

1

2

3

4

5

6

7

8

9

10

11

12

Altitude: 0 – 1000m

0

0

1

Drop-out time: 130 msec

0

1

1

Contactor config.: 400A EH

0

1

TDUV config.: No TDUV

0

Ext. cap TDUV time: 0.2 sec

0

0

*Power-Up Safety: Enable

0