Motor jogging control – Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual
Page 29

Installation and Wiring
3-17
1503-UM051D-EN-P – June 2013
Motor Jogging Control
When used with electrically held contactors, the IntelliVAC allows
close commands every six seconds. This is to ensure the rated
contactor duty cycle of 600 operations per hour is not exceeded.
For motor jogging operations, the second control input, or OPEN
command, will close the contactor for as long as the input is present,
and open the contactor when the input is removed. (Refer to Figure
3.14.) This method will bypass the standard six second motor re-
start delay for jogging purposes only.
*
Refer to Table 3.A for recommended fuse sizing.
N'
N
EMC FILTER
G
P'
P
MOV
3
2
1
EC
-
+
4
TCO
12
11
AUX
CCO
5
6
L1
L2/N
G
+ -
STOP
START
OVERLOAD
CONTROL
POWER
FUSE
*
CONTROL POWER
M-IV
9
10
CLOSE
M-IV
15
16
CONTACTOR
STATUS
M
M-IV
M
+ -
JOG
M-IV
7
8
OPEN
*
Refer to Table 3.A for recommended fuse sizing.
N'
N
EMC FILTER
G
P'
P
MOV
3
2
1
EC
-
+
4
TCO
12
11
AUX
CCO
5
6
L1
L2/N
G
+ -
STOP
START
OVERLOAD
CONTROL
POWER
FUSE
*
CONTROL POWER
M-IV
9
10
CLOSE
M-IV
15
16
CONTACTOR
STATUS
M
M-IV
M
+ -
JOG
M-IV
7
8
OPEN
Figure 3.14 – Motor Jogging Control