Installation and Wiring

3-17

1503-UM051D-EN-P – June 2013


Motor Jogging Control

When used with electrically held contactors, the IntelliVAC allows

close commands every six seconds. This is to ensure the rated

contactor duty cycle of 600 operations per hour is not exceeded.

For motor jogging operations, the second control input, or OPEN

command, will close the contactor for as long as the input is present,

and open the contactor when the input is removed. (Refer to Figure

3.14.) This method will bypass the standard six second motor re-

start delay for jogging purposes only.

*

Refer to Table 3.A for recommended fuse sizing.