Intellivac configuration (cont.) – Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual

Page 32

Advertising
background image

4-2

Setup and Commissioning

1503-UM051D-EN-P – June 2013

IntelliVAC units shipped in a complete MV controller (Bulletin

1500/1900) will be configured to suit the installed application (i.e.

contactor type). The user should verify the settings before energizing

the equipment. Table 4.B defines the settings for each switch.

UP = 1

DOWN = 0

DIP switch SW1

1

2

3

4

5

6

7

8

9

10 11 12

|

|

|

|

Altitude X

1 2 3

12

Power-Up Safety

Y

-1000 to 0

0

0

0

0

Enable

1 to 1000

0

0

1

1

Disable

1001 to 2000

0

1

0

2001 to 3000

0

1

1

10 11

Ext. cap. TDUV time

3001 to 4000

1

0

0

0

0

0.2 sec

4001 to 5000

1

0

1

0

1

0.5 sec

Not defined

1

1

0

1

0

1.0 sec

Not defined

1

1

1

1

1

2.0 sec

9

TDUV config.

0

No TDUV

Drop out time Z

4 5 6

1

TDUV Enabled

50 msec

0

0

0

75 msec

0

0

1

7 8

Contactor Config.

100 msec

0

1

0

0

0

400A Mech. Latch

130 msec

0

1

1

0

1

400A Elec. Held

150 msec

1

0

0

1

0

800A Mech. Latch

175 msec

1

0

1

1

1

800A Elec. Held

200 msec

1

1

0

240 msec

1

1

1

X

The altitude compensation by DIP switch settings applies to Series E 400 amp vacuum contactors only. All 800 amp contactors are adapted

for altitude by altering the return springs. 800 amp contactors are to be set for 1 to 1000m (001 DIP setting).

Y

Available with IntelliVAC using version 2.001 firmware or newer.

Z

By-pass contactors in MV SMC applications must be set for 50 millisecond drop-out time.

Refer to Appendix A for typical drop-out time settings used when power fuses are provided by Rockwell Automation.

IntelliVAC Configuration

(cont.)