Three-wire control – Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual

Page 24

Advertising
background image

3-12

Installation and Wiring

1503-UM051D-EN-P – June 2013

Three-Wire

Control

If using three-wire control, the CLOSE contactor input is maintained

high using two contacts. Momentarily opening this input will cause

the IntelliVAC to open the contactor. Momentarily closing the

START contact will provide a CLOSE command to IntelliVAC

(given that all permissives are satisfied).

In this configuration, the STATUS output acts as a seal-in contact. If a

fault occurs, in addition to cycling control power over to the IntelliVAC

module, the CLOSE command must be removed for a minimum of 4

seconds before being re-applied. Refer to Figure 3.10.

Refer to Table 3.A for recommended fuse sizing.

N'

N

EMC FILTER

G

P'

P

MOV

3

2

1

EC

-

+

4

TCO

12

11

AUX

CCO

5

6

L1

L2/N

G

+ -

STOP

START

OVERLOAD

CONTROL

POWER

FUSE

*

CONTROL POWER

M-IV

9

10

CLOSE

M-IV

15

16

CONTACTOR

STATUS

M

M-IV

M

CAPACITOR

(OPTIONAL)

Refer to Table 3.A for recommended fuse sizing.

N'

N

EMC FILTER

G

P'

P

MOV

3

2

1

EC

-

+

4

TCO

12

11

AUX

CCO

5

6

L1

L2/N

G

+ -

STOP

START

OVERLOAD

CONTROL

POWER

FUSE

*

CONTROL POWER

M-IV

9

10

CLOSE

M-IV

15

16

CONTACTOR

STATUS

M

M-IV

M

CAPACITOR

(OPTIONAL)

Figure 3.10 – Three-Wire Control

Wiring Guidelines

Electrically Held

Contactors (cont.)

Advertising