Installation and Wiring

3-7

1503-UM051D-EN-P – June 2013

Connections

There are three green connectors on the IntelliVAC module for

connections to the control circuitry. Connector plugs are provided

with the module. If additional plugs are required, refer to Chapter 6,
Spare parts.

Control

Power

The IntelliVAC can accept either AC or DC control power. Refer to

Table 1.A for acceptable input power and control signal ratings.

Control power is applied to the module with a two-pole connector

located at the bottom rear portion of the module. Refer to Figures

3.5 and 3.6 for connections. The ‘L1’ connection is intended to be

the ‘Hot’ or ‘+’ side of the control power, and the ‘L2/N’ connection

is intended to be the ‘Neutral’, ‘Return’, or ‘-’ side of the control

power.

In order to meet CE electromagnetic interference requirements, an

external EMC filter must be installed. Refer to Chapter 6 for suitable

EMC filter part number and install per Figure 3.4.

Status

Relays

Status relay connections are accessed with a four-pole connector

located at the bottom front portion of the module. Refer to Figure

3.5 or 3.6 for connections. There are two status relays, each with one

normally-open contact:

Module Status:

Terminals 13 and 14

Contactor Status:

Terminals 15 and 16

Refer to Chapter 5 Monitoring and Troubleshooting for a description

of operation for the relays.

Refer to Table 1.A for electrical ratings of the status relays.

L2/N

L1

CONTACTOR STATUS OUTPUT (N.O.)

MODULE STATUS OUTPUT (N.O.)

POWER INPUT

13

16

15

14

Figure 3.5 – Bottom side connections (Series A)