Chapter objectives, Before you install your input module, Electrostatic damage – Rockwell Automation 1771-IXHR , D17716.5.80 HIGH RESOL.THERMOCOUPLE User Manual

Page 12: Power requirements

Advertising
background image

Chapter

3

3Ć1

Installing the High Resolution

Thermocouple/Millivolt Input Module

This chapter gives you information on:

calculating the chassis power requirement
choosing the module’s location in the I/O chassis
keying a chassis slot for your module
wiring the input module’s field wiring arm
installing the input module

Before installing your input module in the I/O chassis you must:

Action required:

Refer to:

Calculate the power requirements of all modules in each chassis.

Power Requirements

Determine where to place the module in the I/O chassis.

Module Location in the I/O Chassis

Key the backplane connector in the I/O chassis.

Module Keying

Make connections to the wiring arm.

Connecting Wiring and Grounding

Electrostatic discharge can damage semiconductor devices inside this module if
you touch backplane connector pins. Guard against electrostatic damage by
observing the following warning:

CAUTION: Electrostatic discharge can degrade performance or
cause permanent damage. Handle the module as stated below.

Wear an approved wrist strap grounding device when handling the module.

Touch a grounded object to rid yourself of electrostatic charge before handling

the module.

Handle the module from the front, away from the backplane connector. Do not

touch backplane connector pins.

Keep the module in its static–shield bag when not in use, or during shipment.

Your module receives its power through the 1771 I/O chassis backplane from
the chassis power supply. The maximum current drawn by the
thermocouple/millivolt input module from this supply is 750mA (3.75 Watts).

Chapter Objectives

Before You Install Your Input

Module

Electrostatic Damage

Power Requirements

Advertising