Module Calibration

Chapter 7

7Ć3

Table 7.A

Write Block Transfer Word 28

Word/Bit 15 14 13 12 11 10 09 08 07 06 05 04

03

02

01

00

Inhibit Calibration on Channel

Requested Auto-Calibration

Word 28

8

7

6

5

4

3

2

1

Set these bits to

0

Requested

clamp

inhibit

Requested

Save

Values

Requested

Gain Cal.

Requested

Offset Cal.

NOTE: Normally, all channels are calibrated simultaneously (bits 08–15
of word 28 are octal 0). To disable calibration on any channel, set the
corresponding bit 08 through 15 of word 28. To disable the clamp inhibit
function, set bit 06.

4. Queue block transfer reads (BTRs) to monitor for offset calibration

complete and any channels which may have not calibrated successfully.
Refer to Table 7.B.

Table 7.B

Read Block Transfer Word 13

Word/Bit 15 14 13 12 11 10 09 08

07

06

05 04 03

02

01

00

Uncalibrated Channels

Auto-Calibration Status

Word 13

8

7

6

5

4

3

2

1

Cal.

Fault

EEPROM

Fault

Not used

Save to

EEPROM

Complete

Gain Cal.

Complete

Offset Cal.

Complete

5. Proceed to Gain Calibration below.

Gain Calibration

Calibrating gain requires that you apply +100.000mV across each input channel.

Normally all inputs are calibrated together. To calibrate the gain of an input,
proceed as follows:

1. Apply +100.000mV across each input channel as shown in Figure 7.2.