Rockwell Automation 1771-IXHR , D17716.5.80 HIGH RESOL.THERMOCOUPLE User Manual
Page 37
Module Calibration
Chapter 7
7Ć3
Table 7.A
Write Block Transfer Word 28
Word/Bit 15 14 13 12 11 10 09 08 07 06 05 04
03
02
01
00
Inhibit Calibration on Channel
Requested Auto-Calibration
Word 28
8
7
6
5
4
3
2
1
Set these bits to
0
Requested
clamp
inhibit
Requested
Save
Values
Requested
Gain Cal.
Requested
Offset Cal.
NOTE: Normally, all channels are calibrated simultaneously (bits 08–15
of word 28 are octal 0). To disable calibration on any channel, set the
corresponding bit 08 through 15 of word 28. To disable the clamp inhibit
function, set bit 06.
4. Queue block transfer reads (BTRs) to monitor for offset calibration
complete and any channels which may have not calibrated successfully.
Refer to Table 7.B.
Table 7.B
Read Block Transfer Word 13
Word/Bit 15 14 13 12 11 10 09 08
07
06
05 04 03
02
01
00
Uncalibrated Channels
Auto-Calibration Status
Word 13
8
7
6
5
4
3
2
1
Cal.
Fault
EEPROM
Fault
Not used
Save to
EEPROM
Complete
Gain Cal.
Complete
Offset Cal.
Complete
5. Proceed to Gain Calibration below.
Gain Calibration
Calibrating gain requires that you apply +100.000mV across each input channel.
Normally all inputs are calibrated together. To calibrate the gain of an input,
proceed as follows:
1. Apply +100.000mV across each input channel as shown in Figure 7.2.