Module Configuration

Chapter 5

5Ć6

Bit/word descriptions of BTW file words 1 thru 3 (configuration), 4 thru 19
(channel alarm values), and 20 thru 27 (calibration values) are presented in
Table 5.D. Enter data into the BTW instruction after entering the instruction into
your ladder diagram program.

Table 5.D

Bit/Word Definitions for the High Resolution Thermocouple/Millivolt Input

Module

Word

Bits

Description

Word 1

bits 00-02

Input type codes for inputs 1 thru 8 (or 1 thru 4 if bit 06 is set to 1).

Tells the module what type of input device you connected to the

module.

Type

02

01

00

Millivolt input

0

0

0

"B" thermocouple

1

1

1

"E" thermocouple

0

0

1

"J" thermocouple

0

1

0

"K" thermocouple

0

1

1

"R" thermocouple

1

0

1

"S" thermocouple

1

1

0

"T" thermocouple

1

0

0

bits 03-05

Input type codes for inputs 5 thru 8 (bit 06 must be set to 1). Tells the

module what type of input device you connected to inputs 5 thru 8.

Type

05

04

03

Millivolt input

0

0

0

"B" thermocouple

1

1

1

"E" thermocouple

0

0

1

"J" thermocouple

0

1

0

"K" thermocouple

0

1

1

"R" thermocouple

1

0

1

"S" thermocouple

1

1

0

"T" thermocouple

1

0

0

bit 06

When set to 0 bits 00-02 define input type for all channels.

When set to 1 bits 00-02 defines input type for channels 1-4,

and bit 03-05 defines input type for channels 5-8.

bit 07

Enables X10 magnification when millivolt inputs have been selected.

Enabling this feature causes the BTR data to display +30.000mV

around the value selected by word 2. Use the digital filter (word 3) to

stabilize the readings when using this mode.

bit 08

Temperature scale bit, when set, reports temperature in

o

F; when

reset, in

o

C. The module ignores this bit for millivolt inputs.

Bit/Word Descriptions