background image

Module Configuration

Chapter 5

5Ć4

through 8 respectively. Word 28 activates the auto–calibration feature.
Calibration is explained in chapter 7.

The complete configuration block for the block transfer write to the module is
defined in Table 5.C below.

Table 5.C

Configuration Block for the High Resolution Thermocouple/Millivolt Input

Module Block Transfer Write

Word

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

1

Sample Time

T

Z

E

Type

Type

2

Zoom Value for Group 2 (Channels 5-8)

Zoom Value for Group 1 (Channels 1-4)

3

Filter Value for Group 2 (Channels 5-8)

Filter Value for Group 1 (Channels 1-4)

4

Channel 1 Low Alarm Value

5

Channel 1 High Alarm Value

6

Channel 2 Low Alarm Value

7

Channel 2 High Alarm Value

8

Channel 3 Low Alarm Value

9

Channel 3 High Alarm Value

10

Channel 4 Low Alarm Value

11

Channel 4 High Alarm Value

12

Channel 5 Low Alarm Value

13

Channel 5 High Alarm Value

14

Channel 6 Low Alarm Value

15

Channel 6 High Alarm Value

16

Channel 7 Low Alarm Value

17

Channel 7 High Alarm Value

18

Channel 8 Low Alarm Value

19

Channel 8 High Alarm Value

20

Calibration Values for Channel 1

21

Calibration Values for Channel 2

22

Calibration Values for Channel 3

23

Calibration Values for Channel 4

24

Calibration Values for Channel 5

25

Calibration Values for Channel 6

26

Calibration Values for Channel 7

27

Calibration Values for Channel 8

28

Auto-calibration Request Word

Configuration Block for a

Block Transfer Write