Module calibration chapter 7 – Rockwell Automation 1771-IXHR , D17716.5.80 HIGH RESOL.THERMOCOUPLE User Manual

Page 38

Advertising
background image

Module Calibration

Chapter 7

7Ć4

Figure 7.2

Applying 100.00mV for Gain Calibration

1

Do not

use

18 Input 1 (+ lead)

17 Input 1 (- lead)
16 Input 2 (+ lead)
15 Input 2 (- lead)

14 Input 3 (+ lead)

13 Input 3 (- lead)
12 Input 4 (+ lead)
11 Input 4 (- lead)
10 Not Used

9 Not used

8 Input 5 (+ lead)
7 Input 5 (- lead)

6 Input 6 (+ lead)

5 Input 6 (- lead)
4 Input 7 (+ lead)
3 Input 7 (- lead)
2 Input 8 (+ lead)
1 Input 8 (- lead)

Terminal Identification

Terminal Function

Wiring Arm

Cat. No. 1771-WI

18

17

16

1

15

14
13

12

11
10

9
8

7

6
5
4
3

2

100.000mV

Apply

+

-

10531-I

2. After the connections stabilize (about 10 seconds), request the gain

calibration by setting bit 01 in BTW word 28 and sending a block transfer
write (BTW) to the module. Refer to Table 7.A.

When the BTW is sent, all channels are calibrated to +100.00mV.

NOTE: Normally, all channels are calibrated simultaneously (bits 08–15
of word 28 are octal 0). To disable calibration on any channel, set the
corresponding bit 08 through 15 of BTW word 28.

3. Queue BTRs to monitor for gain calibration complete and any channels

which may not have calibrated successfully.