Specifications

Appendix A

A-2

The accuracy of your thermocouple readings depends on:

module accuracy

lead resistance effect

accuracy of the thermocouple

The accuracy of the module is shown in Table A.A and Table A.B at ambient
temperature (25

o

C) and over the temperature range (0–60

o

C).

Use the calibration procedure in Chapter 7 to adjust your module to compensate
for your specific environment.

Table A.A

Thermocouple Range Accuracy Based on Temperatures Above 0

o

C

Thermocouple

Type

Temperature

Range

o

C

Max Error @

Calibration

Temperature (25

o

C)

1

Temperature Drift

o

C/

o

C (0-60

o

C)

or

o

F/

o

F (32-140

o

F)

B

320 to 1800

+1.07

o

C/+1.91

o

F

+0.0746

E

-270 to 1000

+0.50

o

C/+0.90

o

F

+0.0400

J

-210 to 1200

+0.51

o

C/+0.90

o

F

+0.0423

K

-270 to 1380

+0.52

o

C/+0.94

o

F

+0.0640

T

-270 to 400

+0.52

o

C/+0.92

o

F

+0.0183

R

-50 to 1770

+1.14

o

C/+2.00

o

F

+0.0914

S

-50 to 1770

+1.12

o

C/+2.01

o

F

+0.0926

1

Type E, J, K, T, R and S error is specified from 0

o

C (32

o

F) to the maximum range of the

thermocouple. Type B is specified from 600

o

C to maximum range. Error does not include

thermocouple or lead error (see appendix F and page A-3).

Table A.B

Millivolt Range Accuracy

Millivolt

Range

Max Error @ Calibration

Temperature (25

o

C)

Millivolt Drift

-100 to 100 (Normal mode)

+8.85

µ

V

+3.856

µ

V/

o

C

-100 to 100 (Zoom mode)

+5.78

µ

V

+3.856

µ

V/

o

C

Table A.C

Radiated Noise Susceptibility

Radiated Noise

Susceptibility Error

300-1000MHz Circular Wave, Field Strength = 10V/M

< +1%

High Resolution

Thermocouple/Millivolt Input

Module Accuracy