6 - module status and input data, Chapter objectives, Reading data from the module – Rockwell Automation 1771-IXHR , D17716.5.80 HIGH RESOL.THERMOCOUPLE User Manual

Page 32: Module status and input data

Advertising
background image

Chapter

6

6Ć1

Module Status and Input Data

In this chapter you will read about:

reading data from your module

input module read block format

Block transfer read programming moves status and data from the input module
to the processor’s data table in one I/O scan (Table 6.A). The processor user
program initiates the request to transfer data from the input module to the
processor.

During normal operation the module transfers up to 12 words to the processor’s
data table file. The words contain module status and input data from each
channel. During normal operation, when a block transfer length of zero (0)
is programmed, the 1771–IXHR will respond with a default length of 12.

Table 6.A

BTR Word Assignments for the 1771-IXHR Input Module

Decimal Bit

15

14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

1

Not used

Status Codes

2

Inputs overrange

Inputs underrange

3

Inputs > high alarm

Inputs < low alarms

4

Channel 1 input

5

Channel 2 input

6

Channel 3 input

:

:

11

Channel 8 input

12

Cold Junction Temperature in

o

C or

o

F

1

13

Inhibits

Auto-calibration request

1

= Cold junction temperature is provided in 0.1

o

C or 0.1

o

F resolution. The filter time constant (Tau) for

this value is fixed at 6.4 seconds.

Chapter Objectives

Reading Data from the Module

Advertising