18 Installing the Controller

Using Emergency-Stop Switches

When using emergency-stop switches, adhere to the following points:

• Do not program emergency-stop switches in the controller program.

Any emergency-stop switch should turn off all machine power by
turning off the master control relay.

• Observe all applicable local codes concerning the placement and

labeling of emergency-stop switches.

• Install emergency-stop switches and the master control relay in your

system. Make certain that relay contacts have a sufficient rating for your
application. Emergency-stop switches must be easy to reach.

• In the following illustration, input and output circuits are shown with

MCR protection. However, in most applications, only output circuits
require MCR protection.

Using the Lithium Battery

The DataSite controller is equipped with a non-replaceable lithium battery that
is fixed onto a battery seat on the circuit board.

For more information on the battery, see

Lithium Battery on page 54

.

TIP

In most applications input circuits do not require MCR
protection; however, if you need to remove power from all field
devices, you must include MCR contacts in series with input
power wiring.

IMPORTANT

Contact your local Rockwell Automation representative to
arrange for a battery replacement if the battery needs to be
replaced.