Publication 1758-UM001D-EN-P - June 2011

Operating the Controller

53

For 2AO (4…20 mA):

Scan Settings of Equipment

Connected with COMs

There are 1RS232/1RS485-1RS232 serial communications on the DataSite
controller. The CPU of the controller neeeds to be configured in order to read
and write data from equipment connected with the two COMs.

Read mode:

• Read serial equipment data through configuring scan data block

(US1 Block, US2 Block)

• Read serial equipment data through application program

For details, refer to the DataSite Software User Manual, publication

1758-UM002

.

RS485/RS232 Switch

Settings

The serial communication port COM1 of the DataSite controller is designed as
RS485/RS232. The COM1 function can be modified by changing the
configuration, or via an application program. For details, refer to the DataSite
Software User Manual, publication

1758-UM002

.

Communication Parameters

The parameters of the DataSite controller should be configured according to
the application requirements. For details, refer to the DataSite Software User
Manual, publication

1758-UM002

.

Standard value

Current

10000

4.00 mA

20000

8.00 mA

30000

12.00 mA

40000

16.00 mA

50000

20.00 mA

IMPORTANT

COM1 is the common communication port for RS485/RS232.
Only one function can be used when connecting serial
communication equipment. RS485 and RS232 communication
equipment cannot be connected at the same time or else there
will be communication failure.