52 Operating the Controller

Assigned Modbus Register

Addresses of I/O Signals

The I/O points of the controller are:

6AI-3HART-8DI-4DO-2AO-3PI-1RS232-1RS232/1RS485-1Ethernet-12VDC

When we read or write those signals, we only need to read or write the
registers as shown in the following table.

Analog Scaling

For 8AI (4…20 mA)

For 6AI (0…10V):

Signal

Registers

Value range

Meaning

6AI

30001…30006

10000…50000

Unsigned short data, standard value,
readable only.

2HART
(2AI)

30007…30008

10000…50000

Unsigned short data, standard value,
readable only.

8DI

10001…10008

1, 0

BOOL data, readable only

3DI (PI)

10009…10011

1, 0

BOOL data, readable only (when you
use PI as DI)

4DO

00001…00004

1, 0

BOOL data, readable or writable

2AO

40001…40002

10000…50000

Unsigned short data, standard value,
readable or writable

3PI

30011…30016

32-bit int

Unsigned integer data, readable only

Current

Standard value

4.00 mA

10000

8.00 mA

20000

12.00 mA

30000

16.00 mA

40000

20.00 mA

50000

Voltage

Standard value

0.000V

10000

2.500V

20000

5.000V

30000

7.500V

40000

10.000V

50000