Publication 1758-UM001D-EN-P - June 2011

66 Specifications

Flow Measurement

Parameters

The flow measurement specifications apply to 1758-FLO DataSite controllers
only.

Flow Measurement Specifications (for 1758-FLO controllers only)

Attribute

Value

Meter channels

1…8 channels

Meter algorithm

AGA3/AGA7 are optional. The default is AGA3.
Compressibility factor calculation using AGA8.

Clock

Accuracy 0.08s/24h, support calibration

Operation

With the software tools, DS FloConfig and DS DNP3.

Secuity of the system

With special license code for flow computer controller and
password for parameters modification.

Data acquisition cycle

Acquisition cycle of AI-channel is 100 ms. For DI and PI
channels, it is 10 ms.

Flow calculation cycle

1 s

Base conditions

User can change the base conditions.

Compressibility factor
calculation

Three methods of AGA8 optional: Gas analysis, HV-GR-CO2,
GR-CO2-N2

Pressure tap location

Support flange upstream and downstream tap pressure

Transient flow calculation

Supports transient volume hour flow rate calculation in base
conditions and flowing conditions. Supports mass flow rate
calculation. Supports low or zero flow cutoff.

Flow transaction records

Store the hourly and daily historical transaction records
during 35 days. If parameters are changed, a new hourly and
daily record will be logged.

Event records

700 event records

Alarm records

300 alarm records

Accumulative total

Long integer

Overall accuracy

±0.2% F.S.