Wiring for rs485 serial communications – Rockwell Automation 1758-RTU202 DataSite Hardware User Manual User Manual

Page 39

Advertising
background image

Publication 1758-UM001D-EN-P - June 2011

Wiring the Controller

39

Wiring for RS485 Serial Communications

RS485 Port

The following table shows the serial and protocol communication parameters
supported by the RS485 serial port. These parameters are set from the DS
Setting software utility for the 1758-RTU controller or the DS FloConfig
software utility for the 1758-FLO controller.. For details, refer to the DataSite
Software User Manual, publication

1758-UM002

.

The RS485 port of the DataSite controller receives and sends voltage,
measured in microvolts, to other pieces of RS485 equipment. A piece of
RS485 equipment can connect with up to 32 pieces of equipment. The
recommended maximum transmission distance is 1200 m and the two ends
should have terminal resistance.

Signal grounds of the RS485 equipment are not connected together but set
according to the electrical grounding of each piece of equipment. There should
be a difference of a few volts between the grounding voltage of each piece of
RS485 equipment. The RS485 port runs in the two-wire mode.

Serial and protocol communication parameters

Parameter

Engineering value

Baud rate (bps)

2400, 4800, 9600, 19200, 38400, 57600

Communication duplex mode

Half Duplex

Parity

Odd, None or Even

Data bits

7 or 8 bits

Stop bits

1 or 2 bits

Communication protocol

Modbus RTU, Modbus ASCII, DNP3

Protocol mode

Master, Slave (DNP3 supports only Slave mode.)

IMPORTANT

When you use the shielded cable, single-end grounding by the
shielding layer is adopted.