Rockwell Automation 1758-RTU202 DataSite Hardware User Manual User Manual

Page 62

Advertising
background image

Publication 1758-UM001D-EN-P - June 2011

62 Specifications

Analog Output

Attribute

Value

Digital/Analog (D/A)
resolution

16-bit

Power supply

Successive approximation

Output signal range

4…20 mA

Maximum load
Impedance

1000

Ω with 24V DC loop power

400

Ω with 12V DC loop power

Output type

Single ended regulation on positive side with common
negative return

Isolation voltage

70V AC or 100V DC

Absolute accuracy

±0.2% (25 °C with 250

Ω load)

±0.5% (full temperature range, 0…1000

Ω load)

Response time

100 ms typical (10% to 90%)

Noise and ripple, max

0.04%

Transient protection

600 W

HART

Attribute

Value

Modulation

Frequency Shift Keying (FSK)
Logic 1 - 1200 Hz
Logic 0 - 2200 Hz

Data rate

1200 bps

Transmit level

500 mVp-p / 250

Receive sensitivity

120 mVp-p/ on
80 mVp-p/ off

Output impedance

300

transformer isolated

Input impedance

4000

transformer isolated

Load resistor

250

Ω, 1 W max