Rockwell Automation 1758-RTU202 DataSite Hardware User Manual User Manual

Page 27

Advertising
background image

Publication 1758-UM001D-EN-P - June 2011

Wiring the Controller

27

If the outputs are DC, we recommend that you use an 1N4004 diode for surge
suppression, as shown below. For inductive DC load devices, a diode is
suitable. A 1N4004 diode is acceptable for most applications. A surge
suppressor can also be used. See

Recommended Surge Suppressors on page 28

for recommended suppressors. As shown below, these surge suppression
circuits connect directly across the load device.

Suitable surge suppression methods for inductive AC load devices include a
varistor, an RC network, or an Allen-Bradley surge suppressor, all shown
below. These components must be appropriately rated to suppress the
switching transient characteristic of the particular inductive device. See

Recommended Surge Suppressors on page 28

for recommended suppressors.

+24V DC

IN4004 Diode

Relay Or Solid
State DC Outputs

24V DC common

VAC/DC

Out 0
Out 1
Out 2
Out 3
Out 4
Out 5
Out 6
Out 7

COM

(A surge suppressor
can also be used.)

Surge suppression for inductive AC load devices

Output Device

Output device

Output device

Varistor

RC network

Surge
suppressor

Advertising