Publication 1758-UM001D-EN-P - June 2011

Specifications

63

RS232

Attribute

Description

COM port

RS232 serial port (COM1, COM2)
Data Terminal Equipment (DTE)
DB-9P

Baud rate

2400, 4800, 9600, 19200, 38400, 57600

Parity

None, Odd, or Even

Data bits

7 or 8 bits

Stop bit

1 or 2 bits

Duplex

Half-duplex or full-duplex (with RTS/CTS control)

Cable length, max.

15.2 m

Protocol

Modbus RTU/ASCII, DNP3, DS Workbench (only in COM2),
None

Protocol mode

Master, Slave (DNP3 supports only Slave mode.)

RS485

Attribute

Description

COM port

RS485 serial port (COM1)
Data Terminal Equipment (DTE)

Baud rate

2400, 4800, 9600, 19200, 38400, 57600

Parity

None, Odd, or Even

Data bits

7 or 8 bits

Stop bit

1 or 2 bits

Duplex

Half-duplex

Cable length, max.

RS485, 1200 m

Protocol

Modbus RTU/ASCII, DNP3, None

Protocol mode

Master, Slave (DNP3 supports only Slave mode.)