Design a sequential function chart

Chapter 1

If you want to

Then select or set this

member

Data type

Details

Do something one time when the step

becomes active

FS

1

BOOL

The FS bit is on during the first scan of the step.
Typically, we recommend that you use an action with a P1 Pulse (Rising Edge) qualifier

to accomplish this.

Do something while the step is active,

except on the first and last scan

SA

BOOL

The SA bit is on when the step is active except during the first and last scan of the step.

Do something one time on the last scan of

the step

LS

1

BOOL

The LS bit is on during the last scan of the step.
Use this bit only if on the Controller Properties dialog box, SFC Execution tab, you
set the Last Scan of Active Step to Don’t Scan or Programmatic reset.
Typically, we recommend that you use an action with a P0 Pulse (Falling Edge) qualifier

to accomplish this.

Determine the target of an SFC Reset (SFR)

instruction

Reset

BOOL

An SFC Reset (SFR) instruction resets the SFC to a step or stop that the instruction

specifies.
The Reset bit indicates the step or stop where the SFC goes to begin executing again.
Once the SFC executes, the Reset bit clears.

Determine the maximum time that a step

has been active during any of its executions

TMax

DINT

Use this for diagnostic purposes. The controller clears this value only when you set
the Restart Position to Restart at initial step and the controller changes modes or

experiences a power cycle.

Determine if the Timer (T) value rolls over

to a negative value

OV

BOOL

Use this for diagnostic purposes.

Determine how many times a step has

become active

Count

DINT

This is not a count of scans of the step.
• The count increments each time the step becomes active.
• It increments again only after the step goes inactive and then active again.
• The count resets only if you configure the SFC to restart at the initial step. With that

configuration, it resets when the controller changes from program mode to run
mode.

Use one tag for the various status bits of

this step

Status

DINT

For this member

Use this bit

Reset

22

AlarmHigh

23

AlarmLow

24

AlarmEn

25

OV

26

DN

27

LS

28

SA

29

FS

30

X

31

(1) The FS and LS bits are only active during a step’s execution. Once a step finishes executing the code within its actions, the FS or the

LS or both bits are reset. If you reference either of these bits in code outside of the SFC routine in a different part of the project, the
bits are always cleared (0).