Design a sequential function chart Chapter 1

The following table compares the different options for handling the last scan of a
step.

Characteristic

During the last scan of a step, this option does

Don’t scan

Programmatic reset

Automatic reset

Execution actions

Only P and P0 actions execute. They execute

according to their logic.

All actions execute according to their logic.

• P and P0 actions execute according to

their logic.

• All other actions execute in Postscan

mode.

• On the next scan of the routine, the P and

P0 actions execute in Postscan mode.

Retention of data values

All data keeps its current values.

All data keeps its current values.

• Data reverts to its values for postscan.
• Tags to the left of [:=] assignments clear

to zero.

Method for clearing data

Use P and P0 actions.

Use either of these.
• Status bits of the step or action to

condition logic

• P and P0 actions

Use either of these.
• [:=] assignment (non-retentive

assignment)

• Instructions that clear their data during

postscan

Reset of a nested SFC

A nested SFCs remains at its current step.

A nested SFCs remains at its current step.

For the Restart Position property, if you

choose the Restart at initial step option,

then these occur.
• A nested SFC resets to its initial step
• The X bit of a stop element in a nested SFC

clears to zero

Rockwell Automation Publication 1756-PM006F-EN-P - October 2014