Design a sequential function chart Chapter 1

Each action (non-Boolean and Boolean) uses a qualifier to determine when it

starts and stops.

The default qualifier is N Non-Stored. The action starts when the step is activated

and stops when the step is deactivated.

To change when an action starts or stops, assign a different qualifier.

If you want the action to

And

Then assign this

qualifier

Which means

Start when the step is activated

Stop when the step is deactivated

N

Non-Stored

Execute only once

P1

Pulse (Rising

Edge)

Stop before the step is deactivated or when the step is deactivated

L

Time Limited

Stay active until a Reset action turns off this action

S

Stored

Stay active until a Reset action turns off this action
Or a specific time expires, even if the step is deactivated

SL

Stored and Time

Limited

Start a specific time after the step is activated and the

step is still active

Stop when the step is deactivated

D

Time Delayed

Stay active until a Reset action turns off this action

DS

Delayed and

Stored

Start a specific time after the step is activated, even if

the step is deactivated before this time

Stay active until a Reset action turns off this action

SD

Stored and Time

Delayed

Execute once when the step is activated

Execute once when the step is deactivated

P

Pulse

Start when the step is deactivated

Execute only once

P0

Pulse (Falling

Edge)

Turn off (reset) a stored action
• S Stored
• SL Stored and Time Limited
• DS Delayed and Stored
• SD Stored and Time Delayed

---------------------------------------------------->

R

Reset

Choose a qualifier for an

action

Rockwell Automation Publication 1756-PM006F-EN-P - October 2014

29