Design a sequential function chart Chapter 1

Example


When the S_Complete_the_Batch step is active, the S_Open_Outlet action executes. When the action is active, its Q bit turns on.


A ladder Logic routine monitors the Q bit (S_Open_Outlet.Q ). When the Q bit is on, the JSR instruction executes and opens the outlet valve.

You can reuse a Boolean action multiple times within the same SFC.

SFC_ACTION structure

Each action (non-Boolean and Boolean) uses a tag to provide information about

the action. Access this information via either the Action Properties dialog box or
the Monitor Tags tab of the Tags window.

If you want to

Then select or set this

member

Data type

Details

Determine when the action is active

Q

BOOL

The status of the Q bit depends on whether the action is a Boolean action or

non-Boolean action.

If the action is

Then the Q bit is

Boolean

On (1) the entire time the action is active, including the

last scan of the action

Non-Boolean

On (1) while the action is active but
Off (0) at the last scan of the action

To use a bit to determine when an action is active, use the Q bit.

A

BOOL

The A bit is on the entire time the action is active.

Determine how long an action has been

active (milliseconds)

T

DINT

When an action becomes active, the Timer (T) value resets and then starts to count up

in milliseconds. The timer continues to count up until the action goes inactive,

regardless of the Preset (PRE) value.

Use one of these time-based qualifiers: L,

SL, D, DS, SD

PRE

DINT

Enter the time limit or delay in the Preset (PRE) member. The action starts or stops

when the Timer (T) reaches the Preset value.
As an option, enter a numeric expression that calculates the time at runtime.

Rockwell Automation Publication 1756-PM006F-EN-P - October 2014