Force steps Chapter 3

To override the logic of an SFC, you have these options.

If you want to

Then

Override the conditions of a transition each time the SFC

reaches the transition

Force a transition.

Prevent the execution of one or more paths of a

simultaneous branch

Force a simultaneous path.

Force a transition

To override the conditions of a transition through repeated executions of an SFC,

force the transition. The force remains until you remove it or disable forces.

If you want to

Then

Prevent the SFC from going to the next step

Force the transition FALSE.

Cause the SFC go to the next step regardless of transition conditions

Force the transition FALSE.

If you force a transition within a simultaneous branch to be FALSE, the SFC stays

in the simultaneous branch as long as the force is active (installed and enabled).

• To leave a simultaneous branch, the last step of each path must execute at

least one time and the transition below the branch must be TRUE.

• Forcing a transition FALSE prevents the SFC from reaching the last step of

a path.

• When you remove or disable the force, the SFC can execute the rest of the

steps in the path.