Design a sequential function chart Chapter 1

Example

This example shows the use of the SFC Reset (SFR) instruction to restart the SFC
and clear the X bit of the stop element (see

Restart (reset) the SFC

on

page 46

).

If SFC_a_stop.X = on (SFC_a is at the stop) and SFC_a_reset = on (time to reset the SFC) then for one scan (ons[ 0 ] = on):

Reset SFC_a to SFC_a_Step_1

SFC_a_stop.X = 0

SFC_STOP structure

Each stop uses a tag to provide information about the stop element.

If you want to

Then check or set this

member

Data type

Details

Determine when the SFC is at the stop

X

BOOL

• When the SFC reaches the stop, the X bit turns on.
• The X bit clears if you configure the SFCs to restart at the initial step and the

controller changes from program to run mode.

• In a nested SFC, the X bit also clears if you configure the SFCs for automatic reset

and the SFC leaves the step that calls the nested SFC.

Determine the target of an SFC Reset (SFR)

instruction

Reset

BOOL

An SFC Reset (SFR) instruction resets the SFC to a step or stop that the instruction

specifies.
• The Reset bit indicates to which step or stop the SFC will go to begin executing

again.

• Once the SFC executes, the Reset bit clears.

Determine how many times a stop has

become active

Count

DINT

This is not a count of scans of the stop.
• The count increments each time the stop becomes active.
• It increments again only after the stop goes inactive and then active again.
• The count resets only if you configure the SFC to restart at the initial step. With that

configuration, it resets when the controller changes from program mode to run

mode.

Use one tag for the various status bits of

this stop

Status

DINT

For this member

Use this bit

Reset

22

X

31

Rockwell Automation Publication 1756-PM006F-EN-P - October 2014

47