2 - installation and wiring, Before you begin, Power requirements – Rockwell Automation 1790P-4R0 CompactBlock LDX I/O RTD/Resistance Input Module  User Manual

Page 13: 1790d-4r0/t4r0, 1790p-t4r0, Installation and wiring, Chapter

Advertising
background image

1

Publication 1790-UM002A-EN-P

Chapter

2

Installation and Wiring

Before You Begin

This chapter tells you how to:

determine the power requirements for the modules

avoid electrostatic damage

install the module

wire the module’s terminal block

Power Requirements

1790D-4R0/T4R0

The module receives system power from the DeviceNet network. An
auxiliary field supply provides power for the RTD/resistance channels.

1790P-T4R0

The module requires external supplies for both system power and for the
RTD/resistance channels.

Table 2.1 1790D-4R0/T4R0 Power Specifications

Power

Specification

DeviceNet

Supply voltage - 24V dc nominal
Voltage range - 11-28.8V dc
Power dissipation - 1.2W maximum @ 28.8V dc

Field

Supply voltage - 24V dc nominal
Voltage range - 21.6-26.4V dc (+10%)
Power dissipation - 1.5W maximum @ 26.4V dc

Table 2.2 1790P-T4R0 Power Specifications

Power

Specification

PROFIBUS

Supply voltage - 24V dc nominal
Voltage range - 19.2-28.8V dc
Power dissipation - 2W maximum @ 28.8V dc

Field

Supply voltage - 24V dc nominal
Voltage range - 21.6-26.4V dc (+10%)
Power dissipation - 1.5W maximum @ 26.4V dc

Advertising