Over-range flag bits (s8 to s11), Data format – Rockwell Automation 1790P-4R0 CompactBlock LDX I/O RTD/Resistance Input Module  User Manual

Page 33

Advertising
background image

Publication 1790-UM002A-EN-P

Module Data, Status, and Channel Configuration for DeviceNet 3-3

Over-Range Flag Bits (S8 to S11)

Under-range bits for channels 0 through 3 are contained in word 4, bits
8-11. When set (1), the over-range flag bit indicates an RTD temperature
that is greater than the maximum allowed temperature, a resistance input
that is greater than the maximum allowed resistance for the module or an
open channel is detected. The module automatically resets (0) the bit
when the data value is again within the normal operating range.

Data Format

RTD/resistance data is presented in engineering units x1. The engineering
units data format represents real temperature or resistance data provided
by the module. RTD data is reported in either degrees C or degrees F.

Table 3.3 RTD Data Format

RTD Input Type

Range

Data Format

Engineering Units x1

0.1°C

0.1°F

100

Platinum 385

-200 to +850°C

-2000 to +8500

-3280 to +15620

200

Platinum 385

-200 to +850°C

-2000 to +8500

-3280 to +15620

500

Platinum 385

-200 to +650°C

-2000 to +6500

-3280 to +12020

100

Platinum 3916

-200 to +640°C

-2000 to +6400

-3280 to +1184

200

Platinum 3916

-200 to +640°C

-2000 to +6400

-3280 to +1184

500

Platinum 3916

-200 to +640°C

-2000 to +6400

-3280 to +1184

100

Nickel

-60 to +250°C

-600 to +2500

-760 to +4820

120

Nickel

-80 to +260°C

-800 to +2600

-1120 to +5000

200 Nickel

-60C to 250°C

-600 to +2500

-760 to +4820

500 Nickel

-60 to 250°C

-600 to +2500

-760 to +4820

Table 3.4 Resistance Data Format

Resistance Input

Range

Data Format

Engineering Units x1

Resistance 100m

1 to 625

10 to 6250

Resistance 10m

1 to 327

100 to 32700