Channel led indicator operation – Rockwell Automation 1790P-4R0 CompactBlock LDX I/O RTD/Resistance Input Module  User Manual

Page 49

Advertising
background image

Publication 1790-UM002A-EN-P

Diagnostics and Troubleshooting 4-5

Channel LED
Indicator Operation

Individual channel LED indicator operation is shown in the following
table.

Table 4.4 Word Bit Position

Word

Bit Description

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

4

Not Used

S11 S10 S9 S8

Not Used

S3 S2 S1 S0

Table 4.5 Word/Bit Description

Word

Decimal Bit

Description

Read Word 4

Bits 00-03

Underrange for individual channels. Bit 00 corresponds to input
channel 0, bit 01 corresponds to input channel 1 and so on.
When set (1), the input signal is below the input channel’s
minimum range

Bits 04-07

Not used: Set to 0

Bit 08-11

Overrange for individual channels. Bit 08 corresponds to input
channel 0, bit 09 corresponds to input channel 1 and so on.
When set (1), the input signal is above the input channel’s
maximum range, or open RTD is detected

Bit 12-15

Not used: Set to 0

Table 4.6 Individual Channel LEDs Indicator

I/O Channel LED Status Indicator

Status:

Description

Flashing Green/Red

Power up

Off

Off line

Red

On line and no field power

Red

DeviceNet connection and no field power

Flashing Red

Field power and open wire

Green

Field power and valid input

Flashing Red

Input over range, open input

Flashing Red

Input under range

Flashing Red

Recoverable fault