Publication 1790-UM002A-EN-P

Installation and Wiring 2-11

Field Wiring
Connections

System Wiring Guidelines

Consider the following when wiring your system:

General

This product is intended to be mounted to a well-grounded mounting
surface such as a metal panel. Additional grounding connections from
the module’s mounting tabs or DIN rail (if used) are not required
unless the mounting surface cannot be grounded.

Route field wiring away from any other wiring and as far as possible
from sources of electrical noise, such as motors, transformers,
conductors, and ac devices. As a general rule, allow at least 15.2 cm (6
in.) of separation for every 120V of power.

Routing field wiring in a grounded conduit can reduce electrical noise.

If field wiring must cross ac or power cables, ensure that they cross at
right angles.

To ensure optimum accuracy, limit overall cable impedance by
keeping your cable as short as possible. Locate the I/O system as
close to your sensors or actuators as your application will permit.

Tighten terminal screws with care. Excessive tightening can strip a
screw.

Shield Grounding

Use Belden shielded, twisted-pair wire to ensure proper operation
and high immunity to electrical noise. Refer to the following table and
the RTD Wiring Considerations below.

Under normal conditions, the drain wire and shield junction should be
connected to earth ground, via a panel or DIN rail mounting screw at
the module end.

Keep shield connection to ground as short as possible.

If noise persists for a device, try grounding the opposite end of the
cable. (You can only ground one end at a time.)

Refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1, for additional information.

Table 2.4 Belden Shielded Wiring

Configuration

Recommended Cable

(1)

2-wire

Belden™ 9501 or equivalent

3-wire
less than 30.48 m (100ft.)

Belden 9533 or equivalent

3-wire
greater than 30.48 m (100 ft.) or high humidity conditions

Belden 83503 or equivalent

(1) For additional information, see Table 2.5.