3-2 Module Data, Status, and Channel Configuration for DeviceNet

Input Data File

The input data table lets you access RTD input module read data for use
in the control program, via word and bit access. The data table structure is
shown in the tables below.

Input Data Values

Data words 0 through 3 correspond to channels 0 through 3 and contain
the converted analog input data from the input device.

Under-Range Flag Bits (S0 to S3)

Over-range bits for channels 0 through 3 are contained in word 4, bits 0-3.
When set (1), the under-range flag bit indicates an RTD temperature that
is less than the minimum allowed temperature. The module automatically
resets (0) the bit when the data value is again within the normal operating
range.

Table 3.1 Input Data Table

Word/

Bit

15

14

13

12

11

10

9

8

6 5 4

3

2

1

0

0

RTD Input Data Channel 0

1

RTD Input Data Channel 1

2

RTD Input Data Channel 2

3

RTD Input Data Channel 3

4

Not Used

S11

S10

S9

S8

Not Used

S3

S2

S1

S0

Table 3.2 Input Data Table

Word

Decimal Bit Description

Read Word 0

Bits 00-15

Channel 0 input data

Read Word 1

Bits 00-15

Channel 1 input data

Read Word 2

Bits 00-15

Channel 2 input data

Read Word 3

Bits 00-15

Channel 3 input data

Read Word 4

Bits 00-03

Underrange for individual channels - Bit 00 corresponds to input
channel 0, bit 01 corresponds to input channel 1 and so on.

When set (1), the input signal is below the input channel’s
minimum range.

Bits 04-07

Not used: Set to 0

Bits 08-11

Overrange for individual channels - Bit 08 corresponds to input
channel 0, bit 09 corresponds to input channel 1 and so on.

When set (1), the input signal is above the input channel’s
maximum range, or open RTD is detected.

Bit 12-15

Not used: Set to 0.