A - specifications, Environmental specifications, Specifications – Rockwell Automation 1790P-4R0 CompactBlock LDX I/O RTD/Resistance Input Module  User Manual

Page 51: Appendix

Advertising
background image

1

Publication 1790-UM002A-EN-P

Appendix

A

Specifications

Environmental
Specifications

Environmental Specifications

Operating Temperature

0 to 55°C (32 to 131°F)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

Storage Temperature

-40 to 85°C (-40 to 185°F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock)

Relative Humidity

5-90% non-condensing
IEC 60068-2-30 (Test Db, Un-packaged Non-operating)

Operating Altitude

2000m

Vibration

I2g @ 10-500Hz
EC60068-2-6 (Test Fc, Operating)

Shock: Operating

Non-operating

I0g
30g
IEC60068-2-27 Test Ea, (Unpackaged Shock)

Emissions

Group 1, Class A
CISPR 11

ESD Immunity

8kV air discharges
IEC 61000-4-2

Radiated RF Immunity

10V/m with 1kHz sine-wave 80%AM from 80MHz to 1000MHz
10V/m with 200Hz 50% Pulse 100%AM @ 900Mhz
IEC 61000-4-3

EFT/B Immunity

+1kV @ 5kHz on power ports
+2kV @ 5kHz on signal ports
+2kV @ 5kHz on communications ports
IEC 61000-4-4

Surge Transient
Immunity

+1kV line-line(DM) and +2kV line-earth(CM) on power ports
+1kV line-line(DM) and +2kV line-earth(CM) on signal ports
+2kV line-earth(CM) on shielded ports
IEC 61000-4-5

Conducted RF Immunity 10Vrms with 1kHz sine-wave 80%AM from 150kHzto 80MHz

IEC 61000-4-6

Enclosure Type Rating

None (open style)

Mounting

DIN rail or screw

Dimensions

52 x 104 x 42mm (2.03 x 4.07 x 1.64in)

Weight

0.3lb (0.1kg)

Advertising