Determining Module
Update Time

The module update time is defined as the time required for the module to
sample and convert the input signals. The module sequentially samples
the channels in a continuous loop. Module update time is dependent on
the number of input channels and the input filter selection.

The fastest update time occurs with the 500Hz filter enabled. The
following table shows update times for all filter frequencies.

DeviceNet RTD/
Resistance Module
(1790D-4R0/T4R0)

Configuring 1790D-4R0/T4R0 RTD/resistance modules is as easy as
pointing and clicking. RSNetWorx™ lets you simply identify the network
and configure the I/O modules with easy-to-use Electronic Data Sheets
(EDS) files - just point to the field and click on your selection.

To obtain the EDS files you need to configure the modules, go to the
following website: http:/www.ab.com/networks/eds.

EDS files for blocks with matching catalog numbers (for D-Shell and
terminal block versions) are the same. Thus, on the website or in
RSNetWorx for DeviceNet, there may be only one catalog number listed
for both versions.

When using 3rd party configuration software, simply load the EDS files
into the software and follow the vendor’s instructions.

The following example takes you through configuring your RTD/
resistance module with RSNetWorx for DeviceNet, version 3.00 or later.

Table 3.8 Module Update Time

Filter
Frequency

Module Update Time

10 Hz

2.2 seconds

25 Hz

840 milliseconds

50 Hz

420 milliseconds

60 Hz

348 milliseconds

100 Hz

224 milliseconds

250 Hz

88 milliseconds

500 Hz

48 milliseconds

NOTE

Refer to Appendix C to configure the 1790P-T4R0
PROFIBUS module.