Publication 1790-UM002A-EN-P

A-2 Specifications

DeviceNet
Specifications

PROFIBUS DP
Specifications

Specification

Value

Network protocol

I/O Slave messaging:
- Poll command
- Bit Strobe command
- Cyclic command
- COS command

Network length

500 meters maximum @ 125Kbps
100 meters maximum @ 500Kbps

Indicators

1 red/green module status
1 red/green network status

Number of nodes

64 maximum - rotary switch type node address setting

Communication rate

125Kbps, 250Kbps, 500Kbps - auto baud rate selection

Isolation

Type test 1250Vac rms for 60 seconds between field power and
DeviceNet (I/O to logic)

Wiring

Refer to publication DN-6.7.2

PROFIBUS DP Specifications

Network Protocol

PROFIBUS-DP (EN50170)
Communication of the slave with a Class 1 master
Communication of the slave with a Class 2 master

Redundancy

Not supported

Repeater Control Signal RS485 signal
Implementation Type

DPC31

Freeze Mode

Supported

Sync Mode

Supported

Auto Baud Rate

Supported

Fail Safe Mode

Supported

Station Type

Slave

FMS Support

Not supported

Indicators

1 red/green module status
1 red/green network status

Number of nodes

100 maximum - rotary switch type node address setting (0-99)

Network Length/
Communication rate

9.6Kbps @ 1000m (3280ft)
19.2Kbps @ 1000m (3280ft)
45.45Kbps @ 1000m (3280 ft)
93.75Kbps @ 1000m (3280ft)
187.5Kbps @ 1000m (3280ft)
500Kbps @ 400m (1312ft)
1.5mbps @ 200m (656ft)
3mbps @ 100m (328ft)
6mbps @ 100m (328ft)
12mbps @ 100m (328ft)

Isolation

Type test 1250Vac rms for 60 seconds between field power and
PROFIBUS (I/O to logic)