ControlLogix Controller and Memory Board 17

Publication

1756-IN101L-EN-P - June 2008

Installing a Memory Board on a ControlLogix5550 or
ControlLogix5555 Controller

If your ControlLogix5550 or ControlLogix5555 controller requires a different
memory board, install or replace the board as described. The tools required
are:

• #2 Philips screwdriver
• grounding wriststrap

Before you replace the memory board, determine if you must update the
controller firmware.

ATTENTION

Before you install or replace the memory board, disconnect the battery from
the controller. Otherwise, you may damage the memory board.

WARNING

When you connect or disconnect the battery an electrical arc can occur. This
could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.

For Safety information on the handling of lithium batteries, including handling
and disposal of leaking batteries, see Guidelines for Handling Lithium
Batteries, publication

AG-5-4-NOV04

.

Update the Controller Firmware

Controller

Replacing Memory Board
with

Action

ControlLogix5550

No update is required at this time.

ControlLogix5555

Same catalog number of
memory board

No update is required at this time.

Different catalog number of
memory board

For example, you are replacing a
1756-M13 memory board with a
1756-M23 memory board

Before you replace the board
update the firmware of the
controller to a revision that is
compatible with the memory board
that you will install.