Clear a major fault – Rockwell Automation 1756-Lx_Mx ControlLogix Controller and Memory Board Installation Instructions User Manual
Page 38

38 ControlLogix Controller and Memory Board
Publication
1756-IN101L-EN-P - June 2008
Clear a Major Fault
1. Go online with RSLogix 5000 software and get the fault code.
2. Determine what to do next.
Fault Type
Fault Code
Action
1
60
A. Clear the fault.
B. Download the project to the controller.
C. Return the controller to the Run/Remote Run mode.
Follow these steps if the problem persists:
A. Before you cycle power to the controller, record the state
of the OK and RS232 status indicators.
B. Contact Rockwell Automation support.
1
61
A. To get diagnostic information about the fault, see
Knowledgebase document A92558072. To get the
document, see the back of this publication.
B. Clear the fault.
C. Download the project to the controller.
D. Return the controller to the Run/Remote Run mode.
None of the
above
None of the
above
A. Clear the fault.
B. Correct the reason for the fault.
C. Return the controller to the Run/Remote Run mode.
1. PROG.
2. RUN.
3. PROG.
To use the keyswitch of the controller to clear a major fault, turn the keyswitch in the
following sequence: