Conducted RF immunity

IEC 61000-4-6:

• 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80

MHz

Enclosure type rating

None, open style

Isolation voltage

30V (continuous), Basic Insulation Type, RS232 to system

• Controllers type tested to withstand 707V DC for 60 s

Wiring category

(1)

2 - on communications ports

Programming cable

1756-CP3 or 1747-CP3 serial cable

North American temperature
code

T4A

IEC temperature code

T4

Intrinsically safe

No

Replacement battery

1756-L1, 1756-L1M1, 1756-L1M2, 1756-L1M3:

1756-BA1 (0.59 g lithium)

1756-L55, 1756-L55M12, 1756-L55M13, 1756-L55M14,
1756-L55M16, 1756-L55M22, 1756-L55M23, 1756-L55M24:
1756-BA1 (0.59 g lithium)

1756-L61/A, 1756-L62/A, 1756-L63/A:

1756-BA1 (0.59 g lithium)

1756-L61/B, 1756-L62/B, 1756-L63/B, 1756-L64/B, 1756-L65/B:

1756-BA2(0.50 g lithium)

1756-BATM battery module:

1756-BATA (10 g lithium)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial

Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

ControlLogix Controller Common Specifications - 1756-L1, 1756-L1M1,
1756-L1M2, 1756-L1M3, 1756-L55, 1756-L55M12, 1756-L55M13, 1756-L55M14,
1756-L55M16, 1756-L55M22, 1756-L55M23, 1756-L55M24, 1756-L61, 1756-L62,
1756-L63, 1756-L64, and 1756-L65