44 ControlLogix Controller and Memory Board

Publication

1756-IN101L-EN-P - June 2008

ControlLogix Memory Board Specifications - 1756-M1, 1756-M2, 1756-M3,
1756-M12, 1756-M13, 1756-M14, 1756-M16, 1756-M22, 1756-M23, and
1756-M24

Attribute

Value

Temperature, operating

EC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

• 0 … 60 °C (32…140 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40… 85 °C (-40…185 °F)

Relative humidity

EC 60068-2-30 (Test Db, Unpackaged Damp Heat):

• 5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

• 2 g @ 10…500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

• 30 g

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

• 50 g

Emissions

CISPR 11:

• Group 1, Class A

ESD immunity

IEC 61000-4.2:

• 6 kV indirect contact discharge
• 8 kV air discharge

Radiated RF immunity

IEC 61000-4-3:

• 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
• 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
• 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
• 1V/m with 1 kHz line-wave 80% AM from 2.0…2.7 GHz

Enclosure type rating

None, open style

North American temperature
code

T4A

IEC temperature code

T4

Intrinsically safe

No