ControlLogix Controller and Memory Board 37

Publication

1756-IN101L-EN-P - June 2008

RS232

Off

There is no activity.

Solid
green

Data is being received or transmitted.

BAT

Off

For a Series A controller, the controller does not show this
indication.

Solid
green

For a Series B controller, during power-down, the controller is
saving the project to its internal nonvolatile memory. If the BAT
status indicator is solid red before you turn off the power, the
BAT status indicator remains solid red even during the save.

Solid red

If the battery is not installed, install a battery. If the battery is
95% or more discharged, replace the battery.

OK

Off

No power is applied. When ready, turn on power to the
controller.

Flashing
red

If a new controller (just out of the box), the controller requires a
firmware update. See

Update the Controller

.

If the controller is not a new controller (previously in operation),
a major fault occurred. See

Clear a Major Fault

.

Solid red

The controller detected a nonrecoverable fault, so it cleared the
project from memory. See

Clear a Nonrecoverable Fault

.

Solid
green

The controller is ok.

Flashing
green

The controller is storing or loading a project to or from
nonvolatile memory. If the controller has a CompactFlash card,
leave the card in the controller until the OK status indicator turns
solid green.

Indicator

Status

Description