ControlLogix Controller and Memory Board 31

Publication

1756-IN101L-EN-P - June 2008

3. Determine if the memory board has been replaced with a memory

board with a different catalog number.

For example, did you replace a 1756-M13 memory board with a
1756-M23 memory board?

4. Reinstall the previous memory board.

5. Update the firmware of the controller to a revision that is compatible

with the memory board that you intend to install.

See

Firmware Revisions

.

6. Install the new memory board.

7. Determine the color of the OK status indicator.

If

Then

No

The controller is not operational. Contact your Rockwell
Automation representative or local distributor.

Yes

Go to the next step.

If

Then

Solid green

No further actions are required. However, the revision of
firmware must be compatible with your version of RSLogix 5000
software.

Solid red

The controller is not operational. Contact your Rockwell
Automation representative or local distributor.