Choosing the operating mode of the controllers, Choosing the, Operating mode of the controllers – Rockwell Automation 1756-Lx_Mx ControlLogix Controller and Memory Board Installation Instructions User Manual

Page 40: Choosing the operating mode, Of the controllers

Advertising
background image

40 ControlLogix Controller and Memory Board

Publication

1756-IN101L-EN-P - June 2008

Choosing the Operating Mode of the Controllers

IMPORTANT

• All modes send and receive data in response to a message from

another controller.

• All modes produce and consume tags.

No

Do you want to prevent
RSLogix 5000 software from
changing the mode?

Do you want to execute the
logic in the controller?

Do you want the logic to
control the output devices?

Turn the keyswitch to
PROG and then to REM
(Remote Program mode).

Turn the
keyswitch to
PROG (Program
mode).

Turn the keyswitch to RUN
and then to REM
(Remote Run mode).

No

Yes

Do you want to prevent
RSLogix 5000 software from:

• changing the mode
• downloading a project
• performing online edits

Turn the keyswitch to RUN
(Run mode).

No

Yes

Do you need to schedule a
ControlNet network?

No

Yes

Outputs revert to their configured
state for Program mode.

A

This includes Message (MSG) instructions.

B

No

1. Turn the keyswitch to REM.
2. Go online with

RSLogix 5000 software and
choose Test mode.

Yes

B

A

A

A

Yes

Advertising