Rockwell Automation 2711P Creating Modbus Applications User Manual

Page 45

Advertising
background image

Publication 2711P-UM002B-EN-P - March 2007

Installing KEPServer Drivers on Terminal 45

3. If other PanelView Plus terminals exist on the same Ethernet

network, the following error may display:

Error registering name on network (may be duplicate). Change
in system Control Panel and try again.

Ignore this error. It will be corrected during the upgrade. Press
OK to acknowledge error and wait for terminal to reset.

4. On touch or touch/screen terminals, you must calibrate the

touch screen by selecting pointers in all four corners of the
screen and pressing the middle of the screen when prompted.

5. Ignore the following message if it appears. It means RSView ME

is being installed. Do not touch the two buttons that appear
with this message.

Machine edition may be corrupted. Do you want to download
firmware?

6. When the upgrade is complete, a dialog appears requesting you

to remove the compact flash card from the card slot. Remove the
card and press F8 or Exit to reset the terminal.

7. Communication settings are cleared when the terminal is

upgraded. If Ethernet communications is used, reconfigure the
Ethernet communication settings using the values recorded
when preparing the terminal.

8. Replace the .MER files that you backed up before starting the

upgrade or download a new .MER file to the terminal.

9. Load the .MER file and run the project.

TIP

If a USB mouse is available you can acknowledge this
error by selecting OK.

TIP

Kepware drivers were installed on terminal. On
PanelView Plus CE terminals, you can go to the Storage
Card/KEPServer/Drivers folder to verify that the driver dll
exists.

TIP

You can configure your application to start automatically
on power cycle under Startup Options.