Modbus/TCP Address Definitions 65
Holding Registers
Default types are shown in bold.
Holding Registers
Decimal Addressing
Hexadecimal Addressing
Type
Word, Short, BCD
Format
4xxxxx
H4yyyyy
Security
Read/Write
Range
400001 - 465536
H400001 - H410000
Type
Boolean
Format
4xxxxx.bb
H4yyyyy.c
Security
Read/Write
Range
4xxxxx.0 - 4xxxxx.15
4yyyyy.0 - 4yyyyy.F
Type
Float, DWord, Long, LBCD
Format
4xxxxx
H4yyyyy
Security
Read/Write
Range
400001 - 465535
H400001 - H4FFFF
Type
String HiLo Byte Order
Format
400001.2H - 465536.240H
.Bit is string length,
Range 2 - 240 bytes
H400001.2H - H4FFFF.240H
.Bit is string length,
Range 2 - 240 bytes
Security
Read/Write
Range
400001 - 465536
Length 2-240 Bytes
H400001 - H4FFFF
Length 2 - 240 Bytes
Type
String LoHi Byte Order
Format
400001.2L - 465536.240L
.Bit is string length,
Range 2 - 240 bytes
H400001.2L - H4FFFF.240L
.Bit is string length,
Range 2 - 240 bytes
Security
Read/Write
Range
400001 - 465536,
Length 2-240 Bytes
H400001 - H4FFFF,
Length 2 - 240 Bytes