8 - troubleshooting, Objectives, Common errors – Rockwell Automation 2711P Creating Modbus Applications User Manual

Page 59: Runtime errors, Chapter 8, Troubleshooting, Objectives common errors runtime errors, Chapter

Advertising
background image

59

Publication 2711P-UM002B-EN-P - March 2007

Chapter

8

Troubleshooting

Objectives

This chapter lists common errors that occur during application
development as well as errors that occur during runtime.

To diagnose error messages that are generated while developing the
KEPServer driver, refer to the KEPServer online help for the
appropriate driver and refer to the error description.

Common Errors

Some of the most common errors made during application
development are listed below:

• The .mer file was compiled with the wrong .pfe file. See page 16

for details on setting the default project file.

• The KEPServer driver was not downloaded to the terminal. On

PanelView Plus CE terminals, you can verify that the driver is in
the Storage card/KEPServer/drivers folder.

• The wrong serial cable is connected to the PanelView Plus or

PanelView Plus CE terminal. Refer to Chapter 7.

Runtime Errors

The table below lists errors that may occur during runtime. Possible
causes and solutions are provided for each error.

Error

Error Type

Possible Cause

Solution

Device ’<device name> is not
responding

Serious

1. The connection between the device and the

terminal is broken.

2. The communication parameters for the

connection are incorrect.

3. The named device may have been assigned

an incorrect network ID.

1. Verify the cabling between the terminal and

the device. The serial pinout for the
PanelView Plus/PanelView Plus CE terminal
is different than a computer.

2. Verify that the specified communi- cation

parameters match those of the device.

3. Verify that the network ID given to the

named device matches that of the actual
device.

Unable to write to ’<address>’
on device ’<device name>’

Serious

1. The named device may not be connected to

the network.

2. The named device may have been assigned

an incorrect Network ID.

3. The named device is not responding to write

requests.

4. The address does not exist in the PLC.

1. Check the PLC network connections.

2. Verify that the network ID given to the

named device matches that of the actual
device.