Rockwell Automation Publication 2090-IN042A-EN-P - May 2011

12

7. Slowly turn the adjustment wheel until the 2 mm calibration gauge is snug

inside the crimp indenters.

Note: You should still be able to insert and remove the 2 mm calibration
gauge from between the crimp indenters when the gauge is snug.

8. Remove the 2 mm calibration gauge, open the handles, and set the crimp

tool on a flat surface, with the digital display facing up.

9. Press and hold down the On push button.

10. Use the 2 mm calibration gauge to press the Mode push button. Hold the

Mode push button down for 5 seconds.

11. Release the Mode push button.
12. Continue to hold down the On push button for 5 more seconds.
13. Release the On push button.

The digital display value resets to 2.00 mm.

The crimp tool is now calibrated and ready for use.

IMPORTANT

If code E1 displays in the digital display, the calibration was not
successful. Repeat the procedure for calibrating the crimp tool until
2.00 mm shows on the digital display.

Press Down Mode
Button with 2 mm
Calibration Gauge

Press Down On/Off
Button with Finger