Verify the Crimp Tool Accuracy

Before starting any work, perform the steps below to verify the accuracy of the
crimp tool.

1. Turn the adjustment wheel to set the crimp value to 2.00 mm.

2. Close the crimp tool handles to the endstops and hold.
3. Insert the 2 mm calibration gauge between the crimp indenters.

– If the calibration gauge can be inserted, and feels snug without play, the

calibration is OK.

– If the calibration gauge cannot be inserted, or can be inserted but feels

loose and has play, the crimp tool must be calibrated. See

Calibrating

the Crimp Tool on page 11

.

IMPORTANT

For accuracy when setting the crimp value, always turn the adjustment
wheel from a larger number to the actual setting (for example, turn the
adjustment wheel up to 2.10 mm and then turn the adjustment wheel
down to 2.00 mm. Do not start at 1.90 mm and turn the adjustment wheel
up to 2.00 mm).

Insert 2 mm
Calibration
Gauge Here